Modelling
Wind, snow, imposed Q<sub>k</sub> and combinations
#Wind, snow, imposed Qk and combinations
These are the load settings of the model, the same ones Nextra Design keeps in its .nxd file: the peak velocity pressure
and the automatic wind zones of EN 1991-1-4, the snow load of EN 1991-1-3, the concentrated imposed load Qk of
EN 1991-1-1 6.3.1.2, and the national annex and rules the EN 1990 combinations are made with. The analysis engine reads
them exactly as the desktop program does.
Open the dialog with Loads → Advanced (on a phone: Advanced among the Loads tab's tools). The Annex and rules… button in the Combinations step of the Loads tab opens it on its Combinations tab.
The dialog has four tabs. You can change things on several tabs and then press Save once. That saves everything in one step, so one Undo takes it all back. Discard changes goes back to what is saved. The previews ask the engine about the saved project: the model must be a project already (it becomes one at your first edit; projects save themselves), and press Save in the dialog before you preview. Until the model is a project the dialog says "Save the model as a project to see the engine's preview": any edit makes the project.
#Wind

#Peak velocity pressure qp
Choose one of two ways:
- Enter qp: type qp(ze) in kN/m². This works for every annex, and a qp you enter always wins.
- Dutch site (NB): qp is computed by NEN-EN 1991-1-4/NB. This needs the Dutch annex (choose NL on the
Combinations tab).
- Wind area I, II or III (Figure NB.1). You can leave it on From the site and give the province, and a municipality on the Wadden islands gives area I.
- Noord-Holland is split between areas I and II along municipal boundaries, so there you must choose the area yourself.
- Terrain: rural (onbebouwd, the default), built-up (bebouwd) or coast (kust). Area III has no coast column, so the dialog refuses area III with coast.
- ze: the reference height. Empty means the height of the structure.
The dialog shows the qp that follows, for example qp = 0.598 kN/m², area II, rural, ze = 3.50 m. The engine computes it again when it runs, with the same formula (checked against it in the tests).
#Automatic wind
With Automatic wind cases on, the engine makes the wind cases itself. For every wind direction it puts the zones of EN 1991-1-4 7.2 on the building envelope: A–E on the walls and F–J on the roof, with cpe from Tables 7.1–7.5. Each roof cpe set and each cpi becomes a load case of its own, named by the angle (W000_v1_cpi+0.2 …).
- Envelope: by default this is every load panel in the model, or every surface if there are no load panels. The plan size b × d and the height h come from the smallest box around them.
- Roof: From the model (flat, monopitch, duopitch or hipped, recognised from the roof faces), or one of those types.
- Directions: the angles the wind blows to, in degrees. The default is 0, 90, 180, 270. Offset turns them all. Add the diagonals adds 45°, 135°, 225° and 315°. The angles are measured from the building's plan axis, or from global +x if you untick that option.
- cpi: the internal pressure coefficients. Each value makes its own case. The default is +0.2 and −0.3 (EN 1991-1-4 7.2.9(6) Note 2).
- A wind box as the envelope: for a frame without cladding. The four walls and the flat top of a box (b, d, h, bottom, axis, centre) are the faces the wind acts on, and they load the nearest members. Press Box around the structure after a preview to fill the box in from the model.
Preview zones shows what the engine makes for the saved model:
- the number of wind cases;
- for each direction, b, d, e and h/d, with chips to switch direction;
- a plan of the zones with the wind arrow;
- a table of the zones with their areas, cpe,10 and cpe,1. Two values are the two cpe sets of the roof.
In the capture the envelope is the roof panel only, so only F–J appear. The dialog warns about that: draw wall load panels (Loads → Load panels) or use a wind box to load the walls.
Wind load cases lists the model's own wind cases (category Wind). Give one a direction (+x, −x, +y, −y or an angle), the sign of the roof pressure, and cpi if it is not the default. Panel loads given by cpe in that case then act with qp in that direction.
#Snow
Enter sk (kN/m²), and Ce and Ct if they are not 1. The dialog shows s = Ce · Ct · sk (EN 1991-1-3 5.2(3)a, without the shape coefficient). Snow reaches the structure through load panels: a panel load given by a snow factor (the shape coefficient μ, for example μ1 = 0.8) is that factor × s per m² of plan, downwards. See Load panels.
#Imposed Qk

EN 1991-1-1 6.3.1.2(5): the concentrated load Qk is checked on its own, never together with the distributed qk. For every imposed load case the engine can make point-load cases that replace it in the combinations:
- Concentrated Qk: Automatic is on for categories A, B and H when the annex gives a Qk. You can also choose On or Off.
- Qk in kN. Empty means the annex value of the category.
- Positions:
- all 4 edges, or the short or long edges: a point at the middle of each edge (bending) and near its ends (shear);
- members under the panel: on every member under the panel instead, at mid-span and near each end.
- Bays: Split by the members treats each bay between the members as its own panel. Whole panel does not.
- From each end: the distance of the end positions, as a length in m or a ratio from 0 to 0.5. Inset moves the points into the panel.
- Alternative to: makes this case an alternative to another case. It never acts with that case; every combination that has the other case gets a variant with this one instead.
Preview Qk cases lists the cases the engine makes (Q_conc_01 …), with their position and their points. Notes from the engine says where a point was moved to the nearest member or left out.
#Combinations

- National annex: EN, NL, UK or DE, as bundled with the engine. The annex sets γG, γQ, ξ, the
ψ factors of each load category and the Qk values.
- Custom takes a base annex and your own γG,sup, γG,inf, γQ and ξ. A field left empty keeps the base value.
- Consequence class: CC1, CC2 or CC3. It sets KFI, or for NL the factors of NB.5.
- ULS expression: the annex's own (6.10a/b for EN, NL and UK, 6.10 for DE), or 6.10 or 6.10a/b for this model.
- Names: Automatic names the combinations after their leading case when the automatic wind is on, and numbers them otherwise.
- Generate the EN 1990 combinations: on, the engine makes every ULS and SLS combination from the cases. Off, each case
is analysed on its own, plus any combinations you made under Loads → Combinations.
- A model that does not have this setting yet counts as off. Nextra Design reads a file without it the same way, so tick it for a new model.
- Kinds: which kinds are generated (ULS, SLS characteristic, frequent, quasi-permanent).
- Roof imposed load (H) not with snow or wind: EN 1991-1-1 3.3.2(1). This is on by default.
Preview combinations shows every combination the engine will analyse, with its kind and expression, for example [6.10b] 1.2·G + 0.75·Q + 1.5·W000_v1_cpi+0.2. The chips filter by kind. Hover over the expression to see the factors per case.
#Global imperfections

The Combinations tab also holds Global imperfections (EN 1993-1-1 5.3.2), the sway imperfection of EN 1993-1-1 5.3.2 and EN 1992-1-1 5.2. The engine applies it by default. It adds one load case IMP: a force H = φ·N at the top of every column and wall and −H at its foot. N comes from the ULS combination with the largest total compression. IMP is added with factor 1 to every ULS combination.
φ = φ0 · αh · αm, where:
- φ0 is entered as 1/x. The default is 1/200.
- αh = 2/√h, kept between 2/3 and 1.
- αm = √(0.5 (1 + 1/m)).
| Field | What it does |
|---|---|
| On | Off, the run has no IMP case. |
| Structure | Steel / concrete uses φ0·αh·αm. Masonry uses 1/(100√h). Other uses a φ you give (1/x). Without that φ there is no imperfection, so the dialog asks for it. |
| Height h | Empty (auto): from the lowest column foot to the highest column or wall top. The dialog shows its estimate from the model. |
| m | Empty (auto): the engine counts the columns per storey that carry at least half of the storey's mean N. αm and φ are known only after the run, so the dialog shows the range φ0·αh·0.71 to φ0·αh. |
As you type, the dialog shows αh, αm and φ. For example, h = 9 m and m = 2 give αh = 0.667 (2/√9, the lower limit), αm = 0.866 and φ = 1/200 × 0.667 × 0.866 = 0.00289. The engine computes the values again in the run. Its table of φ and H per column is in the run's summary.
IMP acts along +x. With the automatic wind on, it acts along the wind's main direction.
Directions, method, HEd ≥ 0.15 VEd (folded) holds the settings of the engine's older method. That
method added forces per combination, as variants
- Directions: follow the wind, all four, x only, y only, or none.
- Method: equivalent horizontal forces, the buckling-mode shape, or both.
- Skip where HEd ≥ 0.15 VEd: EN 1993-1-1 5.3.2(4).
The engine keeps these settings, but the IMP case does not use them. Changing them does not change the IMP case. A second-order (non-linear) run adds an imperfection shaped like the first buckling mode.
#What the dialog refuses
Every value goes through the same check in the browser and on the server, and the cases are checked against the engine itself. A value the engine would refuse is refused before it is saved, with the reason. Some examples:
| You enter | Why it is refused |
|---|---|
| annex User or FR | the engine has EN, NL, UK, DE and Custom |
| wind area III with terrain coast (also Utrecht + coast) | NB.1 has no coast column for area III |
| a province outside the Netherlands | the area cannot be found: give the wind area |
| no directions, no cpi | no wind case would be made |
| a wind box without its size | the engine would make no wind |
| Qk 0, a ratio above 0.5, a negative inset | not a valid position or load |
| an alternative to a case that is itself an alternative | the engine would ignore it |
| φ0 or φ above 1/20, αh outside 2/3 to 1, m not a whole number | outside the code's range |
| structure Other without φ | the engine would use φ = 0: no imperfection |
#Phone

The dialog fits the width of a phone. The tabs and the Save bar stay in reach.
#Not yet
- The wind zones are shown as a plan and a table in the dialog. They are not drawn in the 3D view yet.
- Your own cpe table file (Nextra Design's coefficients CSV) cannot be used here. The tables of EN 1991-1-4 are used.
- Building envelopes drawn in Rhino (Nextra Design's envelope faces) are kept and analysed, but they can't be edited here.