Timber design (EN 1995)
The EC5 member, CLT, vibration, wall and fire checks.
Timber is checked to EN 1995-1-1, with fire to EN 1995-1-2. Members can be rectangular or circular solid timber, glulam or LVL.
Design strengths use kmod from the combination's load duration and the service class. The partial factor and kcr come from the national annex.
#Member checks
| Group | Checks (clause) |
|---|---|
| Axial | Tension (6.1.2), compression (6.1.4) |
| Bending and axial | Bending with tension (6.2.3), bending with compression (6.2.4) |
| Stability | Flexural buckling with bending (6.3.2), lateral torsional buckling (6.3.3) |
| Shear and torsion | Shear (6.1.7), biaxial shear interaction, torsion (6.1.8), torsion with shear (DIN EN 1995-1-1/NA NCI 6.1.8) |
| Deflection | Instantaneous, net final and final (7.2, Table 7.2) |
| End details | Notch (6.5.2), tenon shear and bearing, fasteners (8.2 to 8.7, indicative) |
| Composite sections | Gamma method (Annex B) |
| I-joists | Finnjoist products (ETA-02/0026) |
Lateral torsional buckling: the effective length l_ef / l (Table 6.1) is 0.9 by default; set it per member, or auto to read it from the moment diagram (uniform load 0.9, point load at mid-span 0.8, constant moment 1.0, cantilever with a uniform load 0.5; other diagrams 1.0). The load on the compression edge adds 2h, as before. The critical stress uses the general formula (6.31); for solid rectangular sections you can choose the simplified (6.32), which is about 12 % less conservative for glulam.
Every deflection row says that it includes shear deformation and how much (about 9 % for a glulam beam of span / depth 13), so you can compare with a bending-only hand calculation.
Default deflection limits are L/300 instantaneous, L/250 net final and L/150 final. For cantilevers they are L/150, L/125 and L/75.
#CLT and laminated surfaces
Surfaces with a layered section are checked layer by layer:
- bending and axial stress in the grain direction,
- shear and rolling shear,
- deflection,
- floor vibration.
EC5 surface design needs a layered section, such as a CLT layup.
#Floor vibration
The vibration check follows EN 1995-1-1 7.3.3 (the 2004 method) and the prEN 1995-1-1 second-generation method. The floor performance levels of the prEN are draft values, marked "verify" in the data. You choose the method in the parameters: 2004, 2025 or both. The required level and the damping ratio are also parameters.
#Walls and floors
| Element | What is checked |
|---|---|
| Stud walls | Racking, studs, hold-downs |
| CLT walls | Overturning models, hold-downs, shear, bearing |
| Joist floors | Joists (normal, I-joist or composite) with vibration |
You draw one vertical surface or a base line with a height. At each run it is replaced by a model. "Show wall model in Rhino" draws what the wall turns into. "Convert to elements" bakes it into ordinary elements.
#Fire
Members use the reduced cross-section method of EN 1995-1-2 4.2.2. CLT uses charring with layer fall-off, by prEN 1995-1-2:2025 or EN 1995-1-2:2004. You set the exposed sides with Nx_FireSides.
#Connections
Fastener groups are designed for dowels, bolts, nails and screws to EN 1995-1-1 section 8. See the Connections page in the Design tab.
#Material library
The library has sawn softwood C14 to C40, sawn hardwood D18 to D80, glulam, Kerto, BauBuche, CLT and OSB3, with sections and CLT layups. Hardwood is designed with its own rules (k_c,90 = 1.0, the hardwood k_90, hardwood charring rates). The D class values are marked VERIFY: check them against EN 338:2016 before relying on a design - the design lists a warning.
Library › Materials › Timber › ⓘ explains which product suits which use and lists common softwood and hardwood species with their usual strength class. The class on the grade stamp of the delivered timber decides.